Violation Detail
Standard Cited: 19100106 B02 V A Flammable liquids.
Inspection Nr: 1776083.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,585.00
Current Penalty: $11,585.00
Issuance Date: 03/05/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 04/21/2025
Gravity: 10
Report ID: 1032500
Contest Date: 03/31/2025
Final Order: 06/20/2025
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/20/2025 | $11,585.00 | 04/21/2025 | Serious | |
Penalty | C: Contested | 04/10/2025 | $11,585.00 | 04/21/2025 | Serious | |
Penalty | Z: Issued | 03/05/2025 | $11,585.00 | 04/21/2025 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(b)(2)(v)(a): Every aboveground storage tank did not have some form of construction or device that will relieve excessive internal pressure caused by exposure to fire. a) On September 11, 2024, and at times prior thereto; employees worked near storage tanks used to store fuel with capacities ranging from 3,954 to 10,477 gallons. The tanks were not constructed with an emergency venting device due to being designed for underground use. Note: Certification of corrective action and supporting documentation are required for this item.