Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1764048.015
Citation: 01003
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $6,453.00
Current Penalty: $3,871.80
Issuance Date: 09/27/2024
Nr Instances: 1
Nr Exposed: 13
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 10/18/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/18/2024 | $3,871.80 | Serious | ||
Penalty | Z: Issued | 09/27/2024 | $6,453.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. On or about July 24, 2024, at an establishment located at 921 South 10th Street in Manitowoc, Wisconsin; in the storage closet on the north wall of the kitchen above the door, a junction box used to power the camera overlooking the kitchen was missing a cover, exposing employees to electrical shock hazards.