Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
Inspection Nr: 1706737.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $13,711.35
Issuance Date: 03/21/2024
Nr Instances: 9
Nr Exposed: 2
Abatement Date: 05/03/2024
Gravity: 10
Report ID: 0626600
Contest Date:
Final Order: 04/12/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/12/2024 | $13,711.35 | 05/03/2024 | Serious | |
Penalty | Z: Issued | 03/21/2024 | $16,131.00 | 04/05/2024 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment shall be consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience: On or about and times prior to October 25, 2023, in the engine room at Labatt Foods in Houston, TX, employees were exposed to struck-by hazards and chemical hazards of ammonia when the employer did not test or replace pressure safety valves (PSV) on ammonia refrigeration compressors at frequency that is in accordance with the manufacturer's recommendations and good engineering practices including, but not limited to: a) The Valve HPR1-5 is a Cyrus Shank 813 relief valve installed in 2018 b) Compressor 4: PRV #9 Valve is a Cyrus Shank 813 relief valve installed March 2018 c) Compressor 4: PRV #10 Valve is a Cyrus Shank 813 relief valve installed March 2018 d) Compressor 3: PRV #9 Valve, C3-9 is a Cyrus Shank 812 relief valve installed March 2015 e) Compressor 3: PRV #10 Valve, C3-10 is a Cyrus Shank 812 relief valve installed March 2015 f) Compressor 2 PRV #9 Valve, C2-9 Cyrus Shank 813 relief valve installed March 2015 g) Compressor 2 PRV #10 Valve, C2-10 Cyrus Shank 813 relief valve installed March 2015 h) Compressor 1 PRV #9 Valve, C1-9 Cyrus Shank 813 relief valve installed March 2018 i) Compressor 1 PRV #10 Valve, C1-10 Cyrus Shank 813 relief valve installed March 2018