Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1689671.015
Citation: 01003
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $15,211.00
Current Penalty: $7,500.00
Issuance Date: 01/26/2024
Nr Instances: 6
Nr Exposed: 6
Abatement Date: 03/01/2024
Gravity: 5
Report ID: 0627500
Contest Date:
Final Order: 02/20/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/20/2024 | $7,500.00 | 03/01/2024 | Other | |
Penalty | Z: Issued | 01/26/2024 | $15,211.00 | 02/14/2024 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.303(g)(1)(i)(A):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: On or about August 07, 2023 the working space between a 240VAC electrical knife switch of a door controller in front of room no.3 was not 36 inches. This condition exposed employees to electrical shock hazards.