Violation Detail
Standard Cited: 19100303 H02 III A General.
Inspection Nr: 1685531.015
Citation: 01003
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $4,465.00
Current Penalty: $4,465.00
Issuance Date: 10/27/2023
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 12/15/2023
Gravity: 5
Report ID: 0522300
Contest Date:
Final Order: 12/04/2023
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 10/27/2023 | $4,465.00 | 12/15/2023 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.303(h)(2)(iii)(A): The installations shall be made with metal-enclosed equipment or shall be enclosed in a vault or in an area to which access is controlled by a lock; a) On or about July 25, 2023, technicians inspecting the mine were exposed to electrical shock and arc flash hazards due to the vaults not being controlled by a lock; the employer did not ensure the vault were locked to other than qualified persons exposing technicians to electrical shock and arc flash hazards.