Violation Detail
Standard Cited: 19100269 N06 I Electric Power Generation, Transmission, and Distribution.
This violation item has been deleted.
Inspection Nr: 1659028.015
Citation: 01003
Citation Type: Serious
Abatement Date: 10/02/2023 2
Initial Penalty: $15,625.00
Current Penalty: $0.00
Issuance Date: 09/13/2023
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 10
Report ID: 0627700
Contest Date:
Final Order: 10/10/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/10/2023 | $0.00 | 10/02/2023 | Serious | |
Penalty | Z: Issued | 09/13/2023 | $15,625.00 | 10/02/2023 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.269(n)(6)(i): Employees were allowed to attach the testing end of grounding cables without attaching the ground-end connection first: On or about March 22, 2023, at a remote location in the backyard of a personal residence, while connecting the cables of fault locator to the cables in a transformer, the employee at the transformer contacted the cables in the transformer before the employee on the opposite end attached the ground cable, exposing employees and contract employees to the hazard of coming in contact with energized/ungrounded parts.