Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1657024.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $15,625.00
Issuance Date: 07/13/2023
Nr Instances: 3
Nr Exposed: 625
Abatement Date: 08/15/2023
Gravity: 10
Report ID: 0420600
Contest Date:
Final Order: 08/07/2023
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/07/2023 | $15,625.00 | 08/15/2023 | Serious | |
Penalty | Z: Issued | 07/13/2023 | $15,625.00 | 08/15/2023 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment. a) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/2023, the employer failed to perform inspections and tests on isolation/stop valve RL-1/V-33. b) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/2023, the employer failed to perform inspections and tests on a Hansen HGV1 Long Neck ?? gauge/service valve which was installed downstream of isolation/stop valve RL-1/V-33 on suction accumulator 33. A Gritty material had accumulated in the gauge/service valve. c) For engine room number 2-3 at the Coca-Cola Auburndale, FL site, on or about 3/16/2023, the employer failed to perform inspections and tests on a Hansen HGV1 Long Neck ?? gauge/service valve which was installed downstream of isolation/stop valve RL-1/V-33 on suction accumulator 33. The gauge was inoperable and unable to be read.