Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1606965.015
Citation: 01003
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $8,806.00
Current Penalty: $8,806.00
Issuance Date: 12/21/2022
Nr Instances: 6
Nr Exposed: 800
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 01/23/2023
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/23/2023 | $8,806.00 | Serious | ||
Penalty | Z: Issued | 12/21/2022 | $8,806.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer shall document that equipment complies with recognized and generally accepted good engineering practices: a) On or about July 11, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, the employer had not documented the ventilation systems in Engine Rooms 5A and 5B exceeded the ASHRAE 15 and/or IIAR 2 Normal Intermittent Ventilation, Continuously Operating Ventilation and Emergency Ventilation requirements. b) On or about July 11, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, the Line #2 Process Area, the HTRL, HTRS and DC ammonia pipelines for Evaporator #17000115 were not labeled. c) On or about July 11, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, in the Line #2 Packaging Area, the HTRL, HTRS and DC ammonia pipelines for the Evaporator #17000118 were not labeled. d) On or about July 11, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, in the Line #4 Processing Area, the HTRL, HTRS and DC ammonia pipelines for each of the two Evaporators were not labeled. e) On or about July 11, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, the Line #9 Marinade Area, the UHRL, UHRS, DC and HG ammonia pipelines for each of the three Evaporators were not labeled. f) On or about July 20, 2022, at the facility located at N4993 6th Drive, West Field, Wisconsin, the Engine Room 4 HTRL pipe line for the High Stage Vessel was not labeled.