Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1582209.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,396.00
Current Penalty: $5,556.00
Issuance Date: 08/15/2022
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 02/28/2023
Gravity: 5
Report ID: 0522300
Contest Date: 09/12/2022
Final Order: 12/28/2022
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 12/28/2022 | $5,556.00 | 02/28/2023 | Serious | |
Penalty | C: Contested | 09/13/2022 | $11,396.00 | 09/19/2022 | Serious | |
Penalty | Z: Issued | 08/15/2022 | $11,396.00 | 09/19/2022 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.305(e)(1):Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: On or about June 10, 2022 the employer did not ensure that electrical enclosures located in the pump house were suitable for the wet or damp locations. Valves of the steam discharge system were in need of repair causing large amounts of steam inside the pump house. The accumulation of the steam caused a large abundance of water to constantly drip onto the electrical components.