Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100335 A02 I Safeguards for personnel protection.

Inspection Nr: 1569321.015

Citation: 01003

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $3,522.00

Current Penalty: $3,522.00

Issuance Date: 06/09/2022

Nr Instances: 1

Nr Exposed: 2

Abatement Date: 07/28/2022

Gravity: 5

Report ID: 0419700

Contest Date:

Final Order: 07/07/2022

Related Event Code (REC): R

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty Z: Issued 06/09/2022 $3,522.00 07/28/2022 Serious  

Text For Citation: 01 Item/Group: 003 Hazard:

29 CFR 1910.335(a)(2)(i):When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: a. In the electrical service room of building 3269 at University Place Apartments, Jacksonville, FL: On or about December 14, 2021, the employer exposed the qualified lead electrician and electrician helper to electrical and arc-flash hazards, in that hazard risk category 1 electrical arc-flash protective equipment insulated hand tools were not used when the lead electrician changed out a 100 amp breaker within the energized 240VAC 600 Amp panel.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close