Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
This violation item has been deleted.
Inspection Nr: 1551622.015
Citation: 01003
Citation Type: Serious
Abatement Status:
Initial Penalty: $10,151.00
Current Penalty: $0.00
Issuance Date: 02/17/2022
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 03/16/2022
Gravity: 10
Report ID: 0523400
Contest Date:
Final Order: 03/15/2022
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/15/2022 | $0.00 | 03/16/2022 | Serious | |
| Penalty | Z: Issued | 02/17/2022 | $10,151.00 | 03/16/2022 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for class of location or for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: (a) On or about September 07, 2021, at the Oxygen tank filling station in the Valve Room, a Class 1 Division 2 Location, the employer did not insure that electrical equipment was intrinsically safe and approved for use near a category 1 flammable gas supply. Specifically, but not limited to the electrical switch controlling the gas filling station, was not rated for use in a hazardous location.
Translate