Violation Detail
Standard Cited: 19100305 J02 IV Wiring methods, components, and equipment for general use.
Inspection Nr: 1522612.015
Citation: 01003
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/10/2021
Nr Instances: 1
Nr Exposed: 15
Abatement Date: 08/31/2021
Gravity:
Report ID: 0215300
Contest Date:
Final Order: 09/01/2021
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 08/10/2021 | $0.00 | 08/31/2021 | Other |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a. On or about March 30, 2021, inside USMS lower level kitchenette of the Federal Operations building, San Juan, PR, the existing branch circuit receptacle, installed within two feet of the sink faucet, did not have ground-fault circuit interrupter (GFCI) protection. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.