Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1457012.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,783.00
Current Penalty: $4,048.10
Issuance Date: 05/06/2020
Nr Instances: 1
Nr Exposed: 100
Abatement Date: 06/02/2020
Gravity: 1
Report ID: 0418100
Contest Date:
Final Order: 06/08/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/08/2020 | $4,048.10 | 06/02/2020 | Serious | |
| Penalty | Z: Issued | 05/06/2020 | $5,783.00 | 06/02/2020 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons of Category 2, 3, or 4 flammable liquids in containers: Carcoustics USA South Inc., Buford, GA - The company had four 55 gallons of diesel fuel, for a total of 220 gallons of category 4 flammable liquid, stored outside of a storage room or cabinet, on or about 1/22/20.