Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1447397.015
Citation: 01003
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,205.00
Current Penalty: $3,470.00
Issuance Date: 03/09/2020
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity: 1
Report ID: 0522300
Contest Date:
Final Order: 04/06/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/06/2020 | $3,470.00 | Serious | ||
| Penalty | Z: Issued | 03/09/2020 | $5,205.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph: On or about November 14, 2019, the 110/220/480 volts, 3 phase electrical junction box located on the southwest wall of the facility adjacent to the company's spray booth was missing the panel door. Employees tasked with completing a two part spray finishing application within the immediate vicinity of the spray booth were not protected from electrical hazards should over spray, dust or other material inadvertently contact the live parts of the electrical equipment.