Violation Detail
Standard Cited: 19261204 D02
Inspection Nr: 1432647.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,145.00
Current Penalty: $12,145.00
Issuance Date: 03/18/2020
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 03/30/2020
Gravity: 10
Report ID: 0215800
Contest Date: 04/08/2020
Final Order: 11/02/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/02/2020 | $12,145.00 | 03/30/2020 | Serious | |
Penalty | C: Contested | 04/13/2020 | $12,145.00 | 03/30/2020 | Serious | |
Penalty | Z: Issued | 03/18/2020 | $12,145.00 | 03/30/2020 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1926.1204(d)(2): The employer did not ensure that proper ventilation equipment was provided and used to obtain acceptable entry conditions: a) On or about 9/20/2019, 304 Front Street, Binghamton, NY, Tank #1: An employee was required to enter a 10,000 gallon gasoline storage tank, to clean and prepare it for removal. The employer did not provide and ensure the use of ventilating equipment such as, but not limited to, forced air ventilation to eliminate the hazard of a flammable atmosphere, resulting in a deflagration and fire when an electric drill was used inside the permit required confined space. Abatement verification is required for this item.