Violation Detail
Standard Cited: 19260706 B Requirements for masonry construction.
Inspection Nr: 1426381.015
Citation: 01003
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $4,048.00
Current Penalty: $4,048.00
Issuance Date: 02/24/2020
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC): A
Gravity: 10
Report ID: 0216000
Contest Date:
Final Order: 03/23/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 02/24/2020 | $4,048.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1926.706(b): All masonry walls over eight feet in height were not adequately braced to prevent overturning and to prevent collapse unless the wall is adequately supported so that it will not overturn or collapse. The bracing shall remain in place until permanent supporting elements of the structure are in place: On or about and times prior to: 8/27/2019 Location: 2nd floor walls a) The buildings exposure CMU walls, approximate wall height 11 3, were not adequately reinforced with rebar, grouted and 2nd floor was not poured with concrete before continuing construction.