Violation Detail
Standard Cited: 19260403 I02 I General requirements.
Inspection Nr: 1399524.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,282.00
Current Penalty: $6,000.00
Issuance Date: 10/30/2019
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 02/28/2020
Gravity: 10
Report ID: 0213900
Contest Date: 12/06/2019
Final Order: 02/25/2020
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 02/25/2020 | $6,000.00 | 02/28/2020 | Serious | |
Penalty | C: Contested | 12/06/2019 | $9,282.00 | 11/05/2019 | Serious | |
Penalty | Z: Issued | 10/30/2019 | $9,282.00 | 11/05/2019 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph: a- 600 James Street, Lakewood NJ: A company employee received electrical shock and burn injuries when working on and around an open, enclosure containing live bus bars feeding a 480 Volt disconnect whose live parts were not guarded against accidental contact. Condition observed on or about 05/07/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.