Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1318378.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,652.00
Current Penalty: $3,991.20
Issuance Date: 11/15/2018
Nr Instances: 1
Nr Exposed: 30
Abatement Date: 12/14/2018
Gravity: 5
Report ID: 0636900
Contest Date:
Final Order: 12/11/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/11/2018 | $3,991.20 | 12/14/2018 | Serious | |
Penalty | Z: Issued | 11/15/2018 | $6,652.00 | 12/14/2018 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. In the flammable storage area employees dispensing products such as, but not limited to isopropyl alcohol into transfer containers without electrical interconnection between the dispensing nozzle and the container. Employees were potentially exposed to a smoke inhalation and burn hazard.