Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1301931.015
Citation: 01003
Citation Type: Serious
Abatement Status:
Initial Penalty: $5,543.00
Current Penalty: $0.00
Issuance Date: 08/21/2018
Nr Instances: 1
Nr Exposed: 305
Abatement Date: 10/09/2018
Gravity: 1
Report ID: 0626300
Contest Date: 09/12/2018
Final Order: 08/19/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 08/19/2020 | $0.00 | 10/09/2018 | Serious | |
| Penalty | C: Contested | 09/14/2018 | $5,543.00 | 10/09/2018 | Serious | |
| Penalty | Z: Issued | 08/21/2018 | $5,543.00 | 10/09/2018 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employers compilation of written process safety information pertaining to the equipment in the process did not include accurate Piping and Instrument diagrams (P&ID's);. (a) The employer did not ensure that the Piping and Instrumentation diagrams (P&ID's) accurately depicted the ammonia detector shut-down levels. The P&ID (sheet 2.4) indicated that the level at which process equipment in the machinery room would be shut-down; was 3,000 ppm; when in fact the detectors were programmed to shut-down at 500 ppm.
Translate