Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1254030.015
Citation: 01003
Citation Type: Serious
Abatement Date: 01/08/2018 2
Initial Penalty: $8,963.00
Current Penalty: $3,571.00
Issuance Date: 11/17/2017
Nr Instances: 3
Nr Exposed: 9
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 12/11/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/11/2017 | $3,571.00 | 01/08/2018 | Serious | |
Penalty | Z: Issued | 11/17/2017 | $8,963.00 | 01/08/2018 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures: On, September 20, 2017, in the following locations, live electrical equipment was exposed to accidental contact: A. Steelyard, Saw #4: Solenoid valves provided on the backside of the horizontal band saw were not provided with covers. One of the valves had electrical tape wrapped around to cover the live contacts. The others were left uncovered with live terminal screws and contacts. B. Switchgear Room for #44: A cover was not provided on a Square D motor starter mounted next to panel LVP1. C. Switchgear Room for #48: The cover provided on the controls for Press #48 was left open.