Violation Detail
Standard Cited: 19260417 A Lockout and tagging of circuits.
Inspection Nr: 1239153.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,408.00
Current Penalty: $6,844.80
Issuance Date: 09/13/2017
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 09/25/2017
Gravity: 10
Report ID: 0522300
Contest Date:
Final Order: 10/05/2017
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/05/2017 | $6,844.80 | 09/25/2017 | Serious | |
| Penalty | Z: Issued | 09/13/2017 | $11,408.00 | 09/25/2017 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged. On or about June 10, 2017, a subcontractors employee was exposed to live electrical current of up to 27KV. The employee was contracted to drill three, 5 inch holes in the concrete floor of a large electrical cabinet located at 375 Victoria Road, Youngstown, Ohio 44515. The electrical current could be isolated and turned off using air switches on a corresponding electrical pole. The air switches were not locked out at the lockout point at the base of the pole.