Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1203878.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,675.00
Current Penalty: $7,461.00
Issuance Date: 07/14/2017
Nr Instances: 5
Nr Exposed: 4
Abatement Date: 08/30/2017
Gravity: 10
Report ID: 0626000
Contest Date:
Final Order: 08/07/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/07/2017 | $7,461.00 | 08/30/2017 | Serious | |
Penalty | Z: Issued | 07/14/2017 | $12,675.00 | 08/30/2017 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP): a. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not document that it complied with its chosen recognized and generally accepted good engineering practice such as ANSI/ASHRAE-15 (American Society of Heating Refrigeration Air-Conditioning and Engineering) (1994), Section 8.13.2, when it failed to set ammonia detectors in the engine room at a value not greater than TLV-TWA (Threshold limit value-time weighted average) exposing employees to toxic hazards of ammonia exposure. b. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not document that it complied with its chosen recognized and generally accepted good engineering practice such as ANSI/ASHRAE-15 (American Society of Heating Refrigeration Air-Conditioning and Engineering) (1994), Section 9.7.8 and ANSI/IIAR-2 (International Institute Ammonia Refrigeration) (1992), Section A.4.1.1, when it failed to discharge anhydrous ammonia not less than 15ft above the adjoining ground level to atmosphere exposing employees to toxic hazards of ammonia exposure. c. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not document that it complied with its chosen recognized and generally accepted good engineering practice such as ANSI/ASHRAE-15 (American Society of Heating Refrigeration Air-Conditioning and Engineering) (1994), Section 8.14(i)and ANSI/IIAR-2 (International Institute Ammonia Refrigeration) (1992), Section 4.4.11, when it failed to install a remote control shut off for mechanical equipment in the refrigerating machinery room (such as but not limited to emergency stop buttons) immediately outside the engine room entrance doors exposing employees to toxic hazards of ammonia exposure. d. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not document that it complied with its chosen recognized and generally accepted good engineering practice such as ANSI/ASHRAE-15 (American Society of Heating Refrigeration Air-Conditioning and Engineering) (1994), Section 8.14(i), when it failed to install a control switch for ventilation fans immediately outside the engine room entrance doors exposing employees to toxic hazards of ammonia exposure. e. On or about 01/17/2017, at the Eddy Packing Inc. facility located in Yoakum Texas, the employer did not document that it complied with its chosen recognized and generally accepted good engineering practice such as ANSI/ASHRAE-15 (American Society of Heating Refrigeration Air-Conditioning and Engineering) (1994), Section 8.13.2, and ANSI/IIAR-2 (International Institute Ammonia Refrigeration) (1992), Section 4.4.1, when it failed to have the ceiling tightly sealed to the walls of the engine room exposing employees to toxic hazards of ammonia exposure.