Violation Detail
Standard Cited: 19100137 C02 VIII Electrical protective equipment.
Inspection Nr: 1184995.015
Citation: 01003
Citation Type: Serious
Abatement Date: 04/30/2017 2
Initial Penalty: $9,959.00
Current Penalty: $4,980.00
Issuance Date: 03/24/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0112600
Contest Date:
Final Order: 04/18/2017
Emphasis:
Substance: 8870
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/18/2017 | $4,980.00 | 04/30/2017 | Serious | |
Penalty | Z: Issued | 03/24/2017 | $9,959.00 | 04/19/2017 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5. Table Talk Pies, 28 Bowditch Dr., Shrewsbury, Massachusetts; On or before October 19, 2016, electrically rated gloves, Class 1 - 7500 volt gloves, used by the journeyman electrician, had not been replaced or retested every six months as required. The gloves available to the electrician were dated January 2014.