Violation Detail
Standard Cited: 19100147 D04 I The control of hazardous energy (lockout/tagout).
Inspection Nr: 1168054.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,471.00
Current Penalty: $7,971.00
Issuance Date: 09/19/2016
Nr Instances: 4
Nr Exposed: 10
Abatement Date: 10/06/2016
Gravity: 10
Report ID: 0626700
Contest Date:
Final Order: 10/07/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/07/2016 | $7,971.00 | 10/06/2016 | Serious | |
Penalty | Z: Issued | 09/19/2016 | $12,471.00 | 10/06/2016 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees: a) At the Digital Room, the employer did not ensure that authorized employees used a lockout device to isolate the energy sources at the main disconnect on a Spartanics, Dye Cutter, Model M500-140, serial number 11088, exposing employees to electrical, and struck by hazards. b) At the Digital Room, the employer did not ensure that authorized employees used a lockout device to isolate the energy sources at the main disconnect on a Spartanics, Dye Cutter, Model M500-117, serial number 10373, exposing employees to electrical, and struck by hazards. c) At the Digital Room, the employer did not ensure that authorized employees used a lockout device to isolate the energy sources at the main disconnect a Spartanics, Dye Cutter, Model M500-200, serial number 13011, exposing employees to electrical, and struck by hazards. d) At the Digital Room, the employer did not ensure that authorized employees used a lockout device to isolate the energy sources at the main disconnect a Spartanics, Dye Cutter, Model M500-181, serial number 12330, exposing employees to electrical, and struck by hazards.