Violation Detail
Standard Cited: 19100119 E03 Process safety management of highly hazardous chemicals.
Inspection Nr: 1165614.015
Citation: 01003
Citation Type: Other
Abatement Date: 07/05/2017 2
Initial Penalty: $11,408.00
Current Penalty: $7,200.00
Issuance Date: 01/26/2017
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): R
Gravity:
Report ID: 0524200
Contest Date:
Final Order: 03/01/2017
Emphasis:
Substance: 2150
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/01/2017 | $7,200.00 | 07/05/2017 | Other | |
Penalty | Z: Issued | 01/26/2017 | $11,408.00 | 04/05/2017 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(e)(3): The process hazard analysis did not address the elements of (i) through (vii) of this paragraph: a) Pinnacle Propane Express, LLC - On or about July 28, 2016, the employer's October 1, 2013 PHA did not address the following conditions: (i) The hazards of the process; (ii) The identification of any previous incident which had a likely potential for catastrophic consequences in the workplace; (iii) Engineering and administrative controls applicable to the hazards and their interrelationships such as appropriate application of detection methodologies to provide early warning of releases. (Acceptable detection methods might include process monitoring and control instrumentation with alarms, and detection hardware such as hydrocarbon sensors.); (iv) Consequences of failure of engineering and administrative controls; (v) Facility siting; (vi) Human factors; (vii) A qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace. This condition exposed employees to fire and explosion hazards.