Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1150653.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,133.00
Current Penalty: $4,000.00
Issuance Date: 11/10/2016
Nr Instances: 3
Nr Exposed: 5
Abatement Date: 12/16/2016
Gravity: 5
Report ID: 0134000
Contest Date:
Final Order: 12/06/2016
Related Event Code (REC):
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/06/2016 | $4,000.00 | 12/16/2016 | Serious | |
Penalty | Z: Issued | 11/10/2016 | $6,133.00 | 12/16/2016 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(ii): Compliance with recognized and generally accepted good engineering practices was not documented: (a) Location - 262 Primrose Street, Haverhill, MA: On or about 5/26/2016, compliance with recognized and generally accepted good engineering practices (RAGAGEP) was not documented in that the doors of the Primrose Engine Room were not provided with panic-type hardware. One applicable RAGAGEP, ANSI/IIAR 2-1999, requires the use of panic type hardware on machinery room doors.