Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1019448.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,500.00
Current Penalty: $3,600.00
Issuance Date: 07/10/2015
Nr Instances: 1
Nr Exposed: 62
Abatement Date: 11/16/2015
Gravity: 5
Report ID: 0420600
Contest Date:
Final Order: 08/04/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/04/2015 | $3,600.00 | 11/16/2015 | Serious | |
Penalty | Z: Issued | 07/10/2015 | $4,500.00 | 08/07/2015 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(i)(D): The employer did not include, in the process safety information compilation, the relief system design and the design basis: a) For the Commercial Warehousing ammonia refrigeration facility located at 101 and 102 Industrial Blvd. in Winter Haven, FL as observed on or about 1/15/2015: Information on the design basis of the relief system was not available such as, but not limited to, calculations to show that the relief valves' sizing and the relief piping sizing were of a safe design to handle all potential release scenarios.