Standard Cited: 19100036 E01 Design and construction requirements for exit routes.
Inspection Nr: 1011410.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,500.00
Current Penalty: $4,125.00
Issuance Date: 05/28/2015
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 09/30/2015
Gravity: 5
Report ID: 0214200
Contest Date:
Final Order: 06/19/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/19/2015 | $4,125.00 | 09/30/2015 | Serious | |
Penalty | Z: Issued | 05/28/2015 | $5,500.00 | 06/26/2015 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.36(e)(1): 29 CFR 1910.36(e)(1): A side-hinged door was not used to connect rooms to an exit route: a. 92 North Main Street, Wharton, NJ - Ingredients Cooler A side hinged emergency exit door was not provided for employees and temporary employees to egress the ingredients cooler where flammable ingredients were stored. Employees entered and exited the ingredients cooler through a single electrically motor operated roll-up door that closed as they entered the cooler. Violation observed on or about January 15, 2015