Violation Detail
Standard Cited: 19100252 C06 II General requirements.
Inspection Nr: 965968.015
Citation: 01002D
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/23/2014
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 09/01/2015
Gravity: 1
Report ID: 0215800
Contest Date: 07/17/2014
Final Order: 10/02/2015
Related Event Code (REC):
Emphasis:
| Failure to Abate | |||||||
|---|---|---|---|---|---|---|---|
| Activity Nr | Issuance | Penalty | Contest | Final Order | |||
| 1130580 | 08/30/2016 | $0.00 | 09/28/2016 | ||||
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| FTA | Z: Issued | 08/30/2016 | $0.00 | 10/18/2016 | 1130580.015 | |
| Penalty | J: ALJ Decision | 10/02/2015 | $0.00 | 09/01/2015 | Serious | |
| Penalty | C: Contested | 07/17/2014 | $0.00 | 07/26/2014 | Serious | |
| Penalty | Z: Issued | 06/23/2014 | $0.00 | 07/26/2014 | Serious |
Text For Citation: 01 Item/Group: 002D Hazard:
29 CFR 1910.252(c)(6)(ii): Indoors, welding or cutting involving zinc-bearing base or filler metals coated with zinc-bearing materials was not done in accordance with 29 CFR 1910.252(c)(3): Welding area, on or about 4/16/14: Mechanical ventilation in a room of 4140 cubic feet was not provided for welders working on carbon steel containing zinc. A welder was exposed to an 8-hour time weighted average of zinc at 0.64 milligrams per cubic meter for the 450 minutes sampled. Abatement certification must be submitted for this item.