Violation Detail
Standard Cited: 19100106 E07 I C Flammable liquids.
Inspection Nr: 569178.015
Citation: 01002D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/07/2013
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 02/14/2013
Gravity: 5
Report ID: 0213100
Contest Date: 02/12/2013
Final Order: 06/03/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 06/03/2013 | $0.00 | 02/14/2013 | Serious | |
| Penalty | C: Contested | 03/05/2013 | $0.00 | 02/14/2013 | Serious | |
| Penalty | Z: Issued | 02/07/2013 | $0.00 | 02/14/2013 | Serious |
Text For Citation: 01 Item/Group: 002D Hazard:
29 CFR 1910.106(e)(7)(i)(c): Locations where flammable vapor-air mixtures may exist under abnormal conditions and for a distance beyond Division 1 locations were not classified Division 2 according to the requirements of subpart S of this part. These locations include an area within 20 feet horizontally, 3 feet vertically beyond a Division 1 area, and up to 3 feet above floor or grade level within 25 feet, if indoors, or 10 feet if outdoors, from any pump, bleeder, withdrawal fitting, meter, or similar device handling Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 F (37.8 C). Pits provided with adequate mechanical ventilation within a Division 1 or 2 area shall be classified Division 2. If only Category 3 flammable liquids with a flashpoint at or above 100 F (37.8 C) or Category 4 flammable liquids are handled, then ordinary electrical equipment is satisfactory though care shall be used in locating electrical apparatus to prevent hot metal from falling into open equipment. a) Flammable storage area- On or about 08/09/12 - Storage area containing approximately 150 gallons of Cat 2 and 3 flammable liquids stored in portable (55gal.) fifty five gallon drums including but not limited to: acetone, recycled acetone, and xylene was not equipped with Class 1 Division 2 electrical components. b) Hand lay-up booth- On or about 8/9/12- 110v-120v electrical fixture was not equipped with a cover.
Translate