Violation Detail
Standard Cited: 19100252 C03 II General requirements.
Inspection Nr: 965968.015
Citation: 01002C
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/23/2014
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 09/01/2015
Gravity: 1
Report ID: 0215800
Contest Date: 07/17/2014
Final Order: 10/02/2015
Related Event Code (REC):
Emphasis:
| Failure to Abate | |||||||
|---|---|---|---|---|---|---|---|
| Activity Nr | Issuance | Penalty | Contest | Final Order | |||
| 1130580 | 08/30/2016 | $0.00 | 09/28/2016 | ||||
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| FTA | Z: Issued | 08/30/2016 | $0.00 | 10/18/2016 | 1130580.015 | |
| Penalty | J: ALJ Decision | 10/02/2015 | $0.00 | 09/01/2015 | Serious | |
| Penalty | C: Contested | 07/17/2014 | $0.00 | 07/26/2014 | Serious | |
| Penalty | Z: Issued | 06/23/2014 | $0.00 | 07/26/2014 | Serious |
Text For Citation: 01 Item/Group: 002C Hazard:
29 CFR 1910.252(c)(3)(ii): A fixed enclosure with a top and not less than two sides which surround the welding or cutting operations did not provide a rate of airflow sufficient to maintain a velocity away from the welder of not less than 100 linear feet (30 m) per minute. Welding area, on or about 4/16/14: Mechanical ventilation as described in 29 CFR 1910.252(c)(3)was not provided for welders working on carbon steel. The ducts at the top of the enclosure did not provide any air flow. Abatement certification must be submitted for this item.