Violation Detail
Standard Cited: 19100124 B04 II
Inspection Nr: 1828555.015
Citation: 01002C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/17/2025
Nr Instances: 6
Nr Exposed: 4
Abatement Date: 11/04/2025
Gravity: 1
Report ID: 0112000
Contest Date: 10/06/2025
Final Order: 02/05/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 02/05/2026 | $0.00 | 11/04/2025 | Serious | |
| Penalty | C: Contested | 10/06/2025 | $0.00 | 11/04/2025 | Serious | |
| Penalty | Z: Issued | 09/17/2025 | $0.00 | 11/04/2025 | Serious |
Text For Citation: 01 Item/Group: 002C Hazard:
29 CFR 1910.124(b)(4)(ii): Mechanical ventilation did not conform to NFPA 34-1995, Standard for Dip Tanks Containing Flammable or Combustible Liquids: Ref. "5-6, Materials of Construction. Exhaust ducts and fasteners shall be constructed of steel." Wash Area: On, or about, July 1, 2025, corrugated poly vinyl chloride (PVC) hose was used in the ventilation system for the oil coating tanks. The tanks contained either Solvent 6733 or Cosmoline 1104 HF, both Category 4 flammable liquids.