Violation Detail
Standard Cited: 19100305 G01 IV B Wiring methods, components, and equipment for general use.
Inspection Nr: 1652240.015
Citation: 01002C
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/08/2023
Nr Instances: 1
Nr Exposed: 6
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 08/31/2023
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/31/2023 | $0.00 | Serious | ||
Penalty | Z: Issued | 08/08/2023 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002C Hazard:
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii)of this section flexible cords and cables may not be used: [B] Where run through holes in walls, ceilings, or floors: On or about February 23, 2023, at the facility located at 410 W Franklin Street, Appleton, WI, two extension cords connected to electrical outlets below the suspended ceiling on Column D6 were routed through openings into the area above the suspended ceiling and then dropped through additional openings in the suspended ceiling to the nearby Supervisors' desks area. The two extension cords were connected to power strips for computer equipment used at the supervisors' desks.