Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1375969.015
Citation: 01002C
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/03/2020
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 03/10/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/10/2020 | $0.00 | Serious | ||
| Penalty | Z: Issued | 02/03/2020 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002C Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: Laundry: On, or about, December 16, 2019, a two wire fan was used in the exhaust duct for the dryer which is classified as a Class III, Division 2 location due to the presence of easily ignitable fibers/flyings. The housing around the motor intake was covered with lint.