Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
Inspection Nr: 1198458.015
Citation: 01002C
Citation Type: Serious
Abatement Date: 02/01/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/15/2017
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0134000
Contest Date:
Final Order: 07/06/2017
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/06/2017 | $0.00 | 02/01/2018 | Serious | |
Penalty | Z: Issued | 06/15/2017 | $0.00 | 07/20/2017 | Serious |
Text For Citation: 01 Item/Group: 002C Hazard:
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, facility siting for the anhydrous ammonia refrigeration process, such as location of ammonia refrigeration process equipment and associated piping in proximity to high pressure boilers subjected the equipment to impact in the event of catastrophic high pressure boiler failure, has not been adequately addressed by the facility through process hazard analysis.