Violation Detail
Standard Cited: 19260502 B02 Fall protection systems criteria and practices.
Inspection Nr: 949254.015
Citation: 01002B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/23/2014
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 05/19/2014
Gravity:
Report ID: 0830500
Contest Date:
Final Order: 05/23/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/23/2014 | $0.00 | 05/19/2014 | Other | |
| Penalty | Z: Issued | 04/23/2014 | $0.00 | 05/19/2014 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1926.502(b)(2): Midrails, screens, mesh, intermediate vertical members, or equivalent intermediate structural members shall be installed between the top edge of the guardrail system and the walking/working surface when there is no wall or parapet wall at least 21 inches (53 cm) high. (a)Twin Peak Erectors Co @ 2617 Broadway, Boulder, CO 80304: On and before November 16th, 2013, the exposing employer did not ensure the midrail was installed midway between the top rail and the walking/working surface in that throughout the building the midrail was 14" and the toprail was 37" from the walking working surface. This condition exposed the employees to a fall from heights of up to approximately 23 feet from the third level. Abatement Note: 1926.760(d)(3) prescribes that perimeter safety cables shall conform to the criteria in 1925.502.