Violation Detail
Standard Cited: 19100119 F03 Process safety management of highly hazardous chemicals.
Inspection Nr: 596378.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 04/01/2013 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/11/2013
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 10
Report ID: 0626700
Contest Date:
Final Order: 02/01/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/01/2013 | $0.00 | 04/01/2013 | Serious | |
Penalty | Z: Issued | 01/11/2013 | $0.00 | 02/13/2013 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.119(f)(3): The operating procedure was not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities. This violation was most recently observed in the N5-Ammonia Recycling Unit of the Dow Chemical in Deer Park, Texas when the Recycle Cartridge Filter Change critical procedure was not reviewed and updated to reflect current operating practices; including operators did not use the IR thermometer gun to verify the housing temperature and did not observe through the sight-glass window to verify isolation valves fully blocked.