Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1652240.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/08/2023
Nr Instances: 1
Nr Exposed: 70
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 08/31/2023
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/31/2023 | $0.00 | Serious | ||
Penalty | Z: Issued | 08/08/2023 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: On or about February 23, 2023, at the facility located at 410 W Franklin Street, Appleton, WI, the potential maximum ampere load of the 11 Zebra Scanner Charging Units and the 2 Honeywell Scanner Charging Units connected to a single outlet of the overhead pendant located above the registry cage, exceeded the Table S-4 Maximum Cord-and-Plug-Connected Load to Receptacle of 16 amperes for a circuit rating of 20 amperes and a receptacle rating of 20 amperes. The total ampere load for the 11 Zebra Scanner Charging Units and the 2 Honeywell Scanner Charging Units is 33.6 amperes.