Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1643242.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/07/2023
Nr Instances: 1
Nr Exposed: 35
Abatement Date: 04/25/2025
Gravity: 10
Report ID: 0112300
Contest Date: 08/01/2023
Final Order: 10/04/2024
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 12/06/2024 | $0.00 | 04/25/2025 | Serious | |
Penalty | F: Formal Settlement | 10/04/2024 | $0.00 | 10/31/2024 | Serious | |
Penalty | C: Contested | 09/13/2023 | $0.00 | 08/10/2023 | Serious | |
Penalty | Z: Issued | 07/07/2023 | $0.00 | 08/10/2023 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.307(c): Electrical equipment in hazardous Class II, Division I, location and Class II, Division II, locations was not intrinsically safe, approved for the hazardous Class II, Division I location and Class II, Division II location, or safe for the hazardous Class II, Division I location and Class II, Division II location: (a) Manual and Spindle Polishing Areas: On or about January 11, 2023, in the area where metal polishing and grinding were performed, electrical equipment including, but not limited to, open motor heaters, electrical outlet boxes, breaker panels, disconnect switches, lighting snap switches, overhead lighting, stand belt grinders/sanders and standing and bench polishers in Class II Division I Locations, were not intrinsically safe, approved for a Class II, Division I location, or safe for a Class II, Division I location. (b)Manual and Spindle Polishing Areas: On or about January 11, 2023, in the area where metal polishing and grinding were performed, electrical equipment including, but not limited to, open motor heaters, electrical outlet boxes, breaker panels, disconnect switches, lighting snap switches, overhead lighting, stand belt grinders/sanders and standing and bench polishers in Class II Division II Locations, were not intrinsically safe, approved for a Class II Division II location, or safe for a Class II, Division II location.