Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1608811.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/16/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity: 5
Report ID: 0317500
Contest Date:
Final Order: 10/19/2022
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 09/16/2022 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Jobsite, D-Pile Area, 11 Lloyd Avenue, Latrobe, PA 15650: Observed on or about July 18, 2022, an electrical (480 volt, 3 phase) panel identified as 'Control Cabinet #6' was left open and plastic was draped over a portion of equipment on the inside (upper left side) of the cabinet. The cabinet housed 480 volt/ 3 phase conductors. Employees working in the area of the cabinet were exposed to electrical shock hazards and fire hazards.