Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1594653.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $3,522.00
Issuance Date: 09/30/2022
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 11/15/2022
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 11/03/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/03/2022 | $3,522.00 | 11/15/2022 | Serious | |
| Penalty | Z: Issued | 09/30/2022 | $0.00 | 10/31/2022 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure. On or about May 10, 2022, at an establishment located at 1102 Jefferson Street in Algoma, Wisconsin; the employer used a flexible cord as a substitute for the fixed wiring used to provide power to a switch and outlet hanging on the side of the 30-inch Rewinder in the Finishing Department. The flexible cord was hardwired into the switch and plugged into a Tripp-Lite SmartPro 120V Line-Interactive Uninterrupted Power Source (UPS). The outlet was providing power to a fan that blows trim waste from the Rewinder.