Violation Detail
Standard Cited: 19100305 J01 IV Wiring methods, components, and equipment for general use.
Inspection Nr: 1578462.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/08/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date: 08/01/2022
Final Order: 11/27/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/27/2022 | $0.00 | Serious | ||
Penalty | C: Contested | 08/02/2022 | $0.00 | Serious | ||
Penalty | Z: Issued | 07/08/2022 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.305(j)(1)(iv): Fixtures installed in wet or damp locations shall be identified for the purpose and shall be so constructed or installed that water cannot enter or accumulate in wireways, lampholders, or other electrical parts. On or about February 15, 2022, at an establishment located at 2099 Badgerland Drive in Green Bay, Wisconsin, on the second floor near the static screen towers and the Panel Operator's Station; a string of portable construction lights and a static screen motor installed in a wet and damp location were not identified for the purpose and were not constructed or installed so that water could not enter or accumulate in wireways, lampholders, or other electrical parts. Panel operators passing through the area to adjust valves or scrape the static screen towers were exposed to electrical shock hazards from water leaking in through a hole in the ceiling and onto a string of portable construction lights and a static screen motor.