Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1471808.015
Citation: 01002B
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/11/2020
Nr Instances: 1
Nr Exposed: 500
Abatement Date: 10/15/2020
Gravity: 10
Report ID: 0112300
Contest Date:
Final Order: 10/08/2020
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/08/2020 | $0.00 | 10/15/2020 | Serious | |
| Penalty | Z: Issued | 09/11/2020 | $0.00 | 10/15/2020 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address the hazards related to facility siting: (a) Fruit Cooler Storage Room: On or about April 3, 2020, the employer located storage racking in close proximity to small diameter liquid ammonia lines, adjacent to evaporator AAU-7, without providing adequate protection from rack loading and unloading activities. This hazardous condition exposed workers to toxic and corrosive hazards when a powered industrial truck struck ammonia piping resulting in an anhydrous ammonia release.