Violation Detail
Standard Cited: 19100119 E01 Process safety management of highly hazardous chemicals.
Inspection Nr: 1361878.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 05/24/2019
Nr Instances: 1
Nr Exposed: 42
Abatement Date: 10/31/2019
Gravity: 10
Report ID: 0317300
Contest Date: 06/14/2019
Final Order: 11/20/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/20/2019 | $0.00 | 10/31/2019 | Serious | |
Penalty | C: Contested | 06/17/2019 | $0.00 | 06/20/2019 | Serious | |
Penalty | Z: Issued | 05/24/2019 | $0.00 | 06/20/2019 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.119(e)(1): The employer did not perform a complete initial process hazard analysis (hazard evaluation) on processes covered by this standard. a) Ethylene Oxide Continuous Plant, Croda-Atlas Point.- On or about November 25, 2018, the employer failed to perform an adequate initial PHA that was based on detailed design P&IDs when its 2015/2016 PHA prior to startup was based on information that pre-dated the Revision 0, set of P&IDs that were issued for construction. Incorrect or outdated P&IDs (e.g. Issued for Construction version) do not allow the employer and the employees involved in conducting PHAs or operating the process to identify and understand the hazards posed by the EO process exposing employees to the hazards of toxic and fire/explosion hazards.