Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1069599.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 03/10/2016 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/04/2015
Nr Instances: 2
Nr Exposed: 76
Related Event Code (REC):
Gravity: 1
Report ID: 0523900
Contest Date:
Final Order: 12/29/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/29/2015 | $0.00 | 03/10/2016 | Serious | |
Penalty | Z: Issued | 12/04/2015 | $0.00 | 03/10/2016 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.119(d)(3)(i)(D): 29 CFR 1910.119(d)(3)(i)(D): The employer did not provide required process safety information for all relief valves and information pertaining to the relief system design and the design basis within the covered process: (a) E-II Building; The employer did not provide process safety information for relief valves on the Delta-T Molecular Sieve (V-064, V-184), E-4 Thin Film Evaporator (V-059 and V-233), F-2 Fractionation Still (V-017), F-3 Fractionation Still (V-045), R-1 Dry-Film Reactor (V-057, V-058, V-059, V-060, V-132, V-045), and the Fuel Blending Nitrogen System (V-004). (b) E-II Building; The employer did not provide, in the process safety information compilation, the relief system design and the design basis for the covered process systems such as, but not limited, to the Liquid Molecular Sieve, the Delta-T Molecular Sieve, and the F-2 and F-3 Fractionation Stills.