Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1019650.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 08/25/2015
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/09/2015
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity: 10
Report ID: 0626700
Contest Date: 07/30/2015
Final Order: 06/05/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/05/2017 | $0.00 | 08/25/2015 | Serious | |
Penalty | C: Contested | 07/30/2015 | $0.00 | 08/25/2015 | Serious | |
Penalty | Z: Issued | 07/09/2015 | $0.00 | 08/25/2015 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP). This violation was most recently observed on or about January 12, 2015, in the Herbicides (Hexazinone) Business Unit at DuPont Plant located in La Porte, Texas, when the employer did not document that atmospheric discharge piping from pressure relief devices on the CHI Condenser Seal Pot and Vacuum Stripper Seal Pot relieved to a safe location and complied with (RAGAGEP) such as the ASME Boiler and Pressure Vessel Code, Section VIII.