Standard Cited: 19100303 F02 General.
Inspection Nr: 1004130.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 03/31/2015 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/12/2015
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0112600
Contest Date:
Final Order: 04/14/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/14/2015 | $0.00 | 03/31/2015 | Serious | |
Penalty | Z: Issued | 03/12/2015 | $0.00 | 03/31/2015 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about 10/27/14, each handle on the QMB Saflex Distribution Panelboard Panel 1 next to the door to the sulfur room was not clearly marked to indicate its purpose, nor located and arranged so the purpose was evident, exposing employees to an electrical hazard. QMB Saflex Distribution Panelboard Panel 1 Circuit 5 was listed twice, and QMB Saflex Distribution Panelboard Panel 1 Circuit 8 was not listed.