Violation Detail
Standard Cited: 19100303 B01 II General.
Inspection Nr: 418783.015
Citation: 01002A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/02/2012
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 11/17/2012
Gravity: 5
Report ID: 0420300
Contest Date:
Final Order: 11/16/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/16/2012 | $0.00 | 11/17/2012 | Serious | |
| Penalty | Z: Issued | 11/02/2012 | $0.00 | 11/17/2012 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from a recognized hazard that was likely to cause death or serious physical harm to employees, in that the employer did not provide conduit with the mechnical strength and durability designed to enclose and protect circuit conductors wiring as required by NEC-2008, Article 300.37. On or about 9 May 2012, 240 volt AC circuit conductor wires were installed as loose conductors running on the ground exposed to damage by lawn maintenance equipment.