Violation Detail
Standard Cited: 19100119 D03 IB Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 315026617
Citation: 01002A
Citation Type: Serious
Abatement Status: X
Initial Penalty: $7,000.00
Current Penalty:
Issuance Date: 04/18/2011
Nr Instances: 3
Nr Exposed: 10
Abatement Date: 05/12/2011
Gravity: 10
Report ID: 1032500
Contest Date: 05/09/2011
Final Order: 03/14/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 03/14/2012 | 05/12/2011 | Serious | ||
| Penalty | Z: Issued | 04/18/2011 | $7,000.00 | 05/12/2011 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(i)(B) The process safety information pertaining to the equipment in the process, does not include piping and instrument diagrams (P&ID): (a) Machine Room Roof, on or about November 29, 2010, and at times prior thereto, the P&ID drawing labeled as Sheet R-057, was incorrect since a valve labeled as "OIL-143-R011" was actually tagged in the field as "OIL-143- R010". (b) On or about November 29, 2010, and at times prior thereto, the P&ID Drawings, such as, but not limited to, those labeled Sheet R-003 and R-004, were not correct since the legend's abbreviations, titles, and color schemes do not match the items on the drawing. An example includes, the Piping Line Type legends show LTRL, but the equipment drawing shows HTRL and both lines are magenta in color. Abatement Note: Abatement certification and documentation ARE required for this item.