Violation Detail
Standard Cited: 19100333 C02 Selection and use of work practices
Inspection Nr: 1751606.015
Citation: 01002A
Citation Type: Serious
Abatement Date: 02/04/2025 2
Initial Penalty: $14,518.00
Current Penalty: $10,000.00
Issuance Date: 11/21/2024
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 10
Report ID: 0317500
Contest Date:
Final Order: 12/13/2024
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/13/2024 | $10,000.00 | 02/04/2025 | Serious | |
Penalty | Z: Issued | 11/21/2024 | $14,518.00 | 12/18/2024 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.333(c)(2):The employer did not ensure that qualified persons were capable of working safely on energized circuits and were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools. Job Site: 149 Devereux Drive, Latrobe, PA 15650, On or about May 29th the employer did not ensure that a qualified person had the ability and knowledge to ensure all live electrical parts on an AAON RN Series Commercial HVAC unit were de-energized before employees were to service the equipment inside of the HVAC unit. Employees were in the process of replacing a faulty compressor on the HVAC unit when one employee came in contact with live 480V wires from the Crank Case Heater. No arc flash personal protective equipment was in use by the employees performing the work.